Why Essex Fire May Not Attend Your Automatic Fire Alarm, and How to Cut False Fire Alarms

Oct 26
6 min read
False fire alarms in Essex showing a smoke detector and fire engine, with guidance on reducing unwanted fire signals.

If your fire alarm sends a signal to the fire service on its own, Essex County Fire and Rescue Service (ECFRS) will usually not send fire engines unless someone rings 999 to confirm a fire, or your building has an exemption. That makes two jobs urgent for any Essex business with a monitored system: make sure a person will call 999 when there is a real fire, and cut false fire alarms so the signals that do come in mean something.

The scale is not small. In its March 2024 campaign release, ECFRS said its crews went to more than 1,240 false alarms in commercial buildings the previous year, 47% of all the incidents it attended at commercial premises.

What the Essex Fire policy actually says

The ECFRS automatic fire alarms page states: "ECFRS will not provide an emergency response to fire calls generated by AFA systems unless:

  • A call is received via 999 confirming a fire or physical signs of fire at the premises in question

  • The building has been granted exemption"

ECFRS uses two terms you will hear from engineers. A false alarm is any activation of an automatic fire alarm (AFA) for a reason other than fire. An unwanted fire signal is a false alarm that reaches the fire service and gets a response.

Not every building is treated the same. ECFRS's technical fire safety policy says premises with a risk to life linked to sleeping accommodation, schools, and premises with an intrinsically high fire risk receive a full and immediate attendance. For all other premises, "mobilisation … will not be initiated upon receipt of a fire call via an AFA system." An ECFRS freedom of information response adds that lower-risk premises face a call challenge: the alarm receiving centre (ARC) is asked to confirm a fire, then tries the occupier, then the keyholder.

If you are unsure which group your building falls into, ask the ECFRS Business Engagement Team (business.safety@essex-fire.gov.uk) rather than assume. Care homes, flats and hotels should check this directly.

What this means for your fire emergency plan

Under article 15 of the Regulatory Reform (Fire Safety) Order 2005, the responsible person must set up procedures to follow in the event of serious and imminent danger. If your plan quietly relies on "the alarm calls the fire brigade", it has a gap. Check that it covers:


  • Who dials 999. Name the role (fire marshal, duty manager, reception) and a deputy. Make it part of staff induction and fire drills.


  • Out of hours. If the building is empty at night or over a weekend, the ARC will try the occupier and keyholder. Keep those contact details current. The ECFRS FOI response says the responsible person must keep premises information held by the ARC up to date.


  • Safe investigation. Whoever checks an activation must do so safely. ECFRS says the responsible person must ensure a safe system of work. Nobody should open a hot door or enter smoke to find out whether a fire is real.

What causes false fire alarms

Nationally, fire and rescue services in England attended 255,047 fire false alarms in the year ending March 2026, 40% of all incidents, according to Home Office figures. Of those, 172,247 were false alarms due to apparatus, roughly two in every three.

ECFRS names system faults, cooking, steam, dust, and smoking or vaping as common causes. Most can be managed on site once you know which device is operating and why.

Cause

Typical example

Practical fix

Cooking fumes

Toaster in an office kitchenette under a smoke detector

Cook only in designated areas with suitable detection; use extraction and keep doors closed

Steam

Shower room or kettle point next to a corridor detector

Ventilate and keep the outer doors closed; review detector type

Smoking and vaping

Staff vaping in a stairwell or toilet

Allow it only in designated places with detection suited to the risk

Contractors

Dust from drilling, sanding or hot work

Brief contractors; cover or isolate detectors during work and reinstate after; keep a manual call point available

Testing and maintenance

Weekly test sent to the ARC as a real alarm

Put the system "off watch" with your monitoring centre before any test

System faults

A fault on a device or the panel

Report faults shown on the panel to your maintainer and keep to six-monthly servicing

Causes and fixes from ECFRS guidance.

How to reduce false fire alarms: a practical fix list

  1. Investigate every activation before you reset. Fire Industry Association guidance advises silencing the alarm but not resetting the panel, because resetting can clear the information you need. Read the panel, go to the device and work out why it operated.

  2. Log it. Record the date, time, device, cause and action taken in the system logbook. Patterns in time and location usually point to the fix.

  3. Take the system off watch before tests. Ring your ARC first, every time.

  4. Control the obvious triggers. Cooking, steam, vaping and contractor work, as in the table above.

  5. Review detector type and position with your engineer. ECFRS suggests reassessing detector location, type and sensitivity. BS 5839-1:2025 places more emphasis on multi-sensor detectors where point smoke detectors carry a higher false alarm risk.

  6. Ask about a delay or filtering. ECFRS lists an investigation period before the signal goes to the ARC, and coincidence detection, where two devices must operate before a signal is sent. ECFRS advises discussing both with a competent fire alarm engineer.

  7. Keep servicing on schedule. BS 5839-1 recommends servicing at intervals of about six months.

What BS 5839-1:2025 changes for false alarms

BS 5839-1:2025, the code of practice for fire alarm systems in non-domestic premises, came into effect on 30 April 2025 and replaced the 2017 edition, as the FIA and the IET both confirm. Owners will notice these points at their next service:

  • A False Alarm Notice. A new label, on or next to the control panel of systems with an automatic connection to the fire service through an ARC, reminds staff that the system is live and the ARC must be told before tests.

  • Investigate every false alarm. The handover organisation should advise the user to arrange suitable investigation each time a false alarm occurs.

  • A false alarm rate check at every service. The FIA guide to the changes explains that the rate is worked out as false alarms per 100 automatic detectors over the previous 12 months. Above 4 per 100, a preliminary investigation is needed. On systems with more than 40 detectors, an average above 5 per 100 calls for an in-depth investigation. These thresholds are unchanged from 2017; the new Annex F shows how to calculate them.

Worked example: a building with 60 automatic detectors and 4 false alarms in the last 12 months has a rate of 100 × 4 ÷ 60 = 6.7 per 100 detectors. That is over both thresholds, so the system needs an in-depth investigation.

Can repeated false alarms lead to enforcement?

Yes. Article 17 of the Fire Safety Order requires the responsible person to keep fire safety equipment "maintained in an efficient state, in efficient working order and in good repair." ECFRS says a system with an unacceptably high false alarm rate that is not investigated may be regarded as non-compliant, and that "failure to reduce your false alarms may result in legal enforcement action."

Frequently asked questions

Do businesses in Essex get charged for false fire alarms?

The ECFRS automatic fire alarms page does not mention charges. The risk it does describe is enforcement action if false alarms are not reduced. Policies change, so check with ECFRS if you have had several call-outs.

Will Essex Fire come if my alarm goes off at night in an empty office?

Not on the automatic signal alone, unless the building has an exemption. The ARC will try to reach the occupier and then the keyholder to confirm a fire. Make sure your keyholders know they may be the ones who need to call 999.

Does this apply to care homes and blocks of flats?

ECFRS's policy gives an immediate attendance to premises with a risk to life linked to sleeping accommodation. Confirm your building's status with the ECFRS Business Engagement Team rather than assume it is covered.

Book a fire alarm service or false alarm survey

Advanced Protection designs, installs and services fire alarm systems across Colchester and Essex, including fire alarm installs on tower blocks and work on large social housing contracts. A job starts with an initial consultation, followed by design and a written quote, then installation and testing, and a walkthrough so your staff know how the system works. If your system keeps going off, we can find the cause, check it against BS 5839-1:2025 and recommend the fix. See our fire alarm servicing and installation page or our fire alarm services in Colchester, call 01255 860018, or use our contact page.